Graduation Year

2013

Document Type

Thesis

Degree

M.S.C.E.

Degree Granting Department

Civil and Environmental Engineering

Major Professor

Rajan Sen

Co-Major Professor

Austin G. Mullins

Keywords

Epoxy, Infrared Thermography, Masonry Strengthening, Pull-off Testing, Thermal Cycling, Thermocouple

Abstract

This study presents results from non-destructive testing to evaluate the degradation of the CFRP-masonry bond using thermal imaging. The goal of the research was to identify locations where there was evidence of bond deterioration that could subsequently be verified through destructive pull-off testing.

Four full-scale masonry walls were built outdoors at the University of South Florida in 1995 to evaluate the effectiveness of CFRP for repairing settlement damage. Two of the settlement-damaged walls were repaired using single layer, commercially available unidirectional CFRP systems that used Tonen (wall 3) and Henkel (wall 2) epoxies. These two walls were the subject of this investigation.

Before non-destructive tests were initiated, historical site data on temperature, humidity and rainfall variation was compiled. Over seventeen years, the walls experienced ambient temperatures as high as 98°F and as low as 25°F. The average rainfall in Tampa is about 34 inches and the annual average high humidity is around 87%#37;. Because of the high temperature and humidity, the CFRP-masonry bond was exposed to a particularly aggressive environment.

Three types of thermal evaluation were carried out: thermocouple monitoring and both passive (solar) and active (localized heating) infrared thermal imaging. Twenty-four thermocouples were used to observe the spatial variations in temperature on the wall. Data showed that the surface temperatures of the wall are uneven with one end being hotter than the other. Measurements indicated that the wall temperatures went as high as 103°F during the week of data collection in late March and early April of 2012. In contrast, the highest ambient temperature over the same period was 92°F. The high temperature experienced by the wall is below the glass transition temperature for the epoxies, which ranges from 140°F to 180°F.

A FLIR Tau 320 thermal imaging camera was used to identify localized de-bonding. Solar radiation heated the walls and the goal of thermal imaging was to detect hot spots which are indicative of de-bonding. Although this technique is ideal for exterior applications, initial attempts were unsuccessful. Once de-bonds were located by sounding, the camera was capable of confirming two hot spots on wall 2.

A thermal scanner built by the university from a series of ten Omega OS137 thermal sensors was used to obtain more complete thermal images of the walls. This scanner had a heating element which supplied heat and allowed for active thermography. The scanner detected 16 hot spots not seen with the thermal camera. Ten of the twelve spots on wall 2 are concentrated on a region of the wall which experienced the highest daily changes in temperature, which indicates that higher thermal and environmental cycling has caused greater de-bond.

Based on the number of hot spots found using both active and passive thermography the Tonen epoxy is performing better than the Henkel epoxy. In general, the bond has endured; however, there are a few localized areas that have de-bonded. Pull-off tests are recommended on walls 2 and 3. Five locations in regions suspected to have poor bond and five locations in regions suspected to have good bond are identified for each wall.